XWE-3000A Transformer Demagnetization Tester
About the product
This instrument is specialized equipment for eliminating residual magnetism in large power transformers, with demagnetization and verification demagnetization functions. It plays an extremely important role in protecting transformers from the impact of excitation inrush current, ensuring safe operation, and prolonging transformer life.
After voltage ratio, DC resistance measurement, and no-load test, residual magnetism will remain in the iron core of power transformers. If residual magnetism is not treated, it may have many adverse effects on the relay protection devices and primary equipment of power transformers. Excessive excitation inrush current can cause the transformer to fail to close, as well as mechanical vibration of the transformer itself, resulting in displacement of the winding structure, affecting the service life of the power transformer and even causing permanent damage.
For this purpose, our company has developed a series of transformer demagnetization products. We are one of the earliest manufacturers in China to develop and produce demagnetization instruments, accumulating a wealth of practical experience.
The demagnetization analyzer for power transformers is a new-generation demagnetization analyzer independently developed by our company. By adopting advanced and reasonable composite current method technology, it is possible to quickly demagnetize power transformers and quantify residual magnetism detection. Detecting and eliminating residual magnetism is automatically completed in one go.
Main technical features
- The instrument adopts an advanced composite current demagnetization method, with minimal current impact during the demagnetization process.
- It has two modes: manual demagnetization and automatic demagnetization.
- It has the functions of initial remanence detection and remanence detection after demagnetization, and can complete demagnetization and remanence measurement with one wiring.
- The progress percentage of the demagnetization process and demagnetization progress indicator bar are intuitive and clear, quantifying the remanence rate and displaying the remanence curve before and after demagnetization.
- The wiring is simple and can be directly demagnetized using the test line of the DC resistor.
- Adopting digital current adjustment, the control accuracy of current is high.
- Adopting a 5-inch color touch screen control, it is easier to operate, and the system interface can switch between Chinese and English.
- Automatic storage of test results, complete recording of data before and after demagnetization, without the need for manual storage.
- The report can be printed directly and stored on a USB drive.
- The analysis software has a high degree of humanization and intelligence in management. After setting the parameters, all measurement work can be completed with just one key press.
- The software interface is simple and intuitive, with clear menus for analysis, storage, report export, printing, and more.
Main technical indicators
- Input type: Current method
- Output voltage: Vpp-40V, automatically adjusted during testing
- Output current: 5A, 4A, 3A, 2A, 1A, can be freely selected
- Residual magnetism: 0-100%
- Demagnetization progress: 0-100%
- Demagnetization effect: residual magnetization rate ≤5%
- Minimum resolution: 0.1%
- Power supply voltage: AC100V-240V±10%
- Frequency: 50Hz/60Hz
- Working environment: -10℃~50℃ ≤ 85%RH
- Weight: 6kg
Main features of testing and analysis software
- Adopting an embedded system, there is no risk of software poisoning.
- Adopting a directory-based storage method for test data, the management of test data is simple and convenient.
- The testing system can directly print data.
- Support USB data export function.
- The software has a high degree of intelligence, and after the input and output signals are connected, all measurement work can be completed with just one key press.
- The software interface is simple, intuitive, and practical.